Sanyo SANUPS E11A102A Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Unterbrechungsfreie Stromversorgungen (USVs) Sanyo SANUPS E11A102A herunter. Sanyo SANUPS E11A102A User's Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - E11A102A

Uninterruptible Power Supply SANUPS E11A102A Instruction Manual M0007084E

Seite 2

− 7 − (5) Insulation testing Before testing indoor wiring insulation, shut down the UPS and disconnect the input and output cables. Conducting an in

Seite 3 - SAVE THESE INSTRUCTIONS

− 8 − 4. Overview The SANUPS E11A is a stationary-type uninterruptible power supply designed to provide high-quality, stable AC power to critical e

Seite 4 - PRECAUTIONS

− 9 − EXT.BATT17.32440MAIN SW863.39 5. External Dimensions and Part Names 5.1 Front and Back Panels Depth: 408 mm (1

Seite 5 - 2. Wiring Precautions

− 10 − 5.2 Control Panel and Indicators Functions No. Label Status display Lit Not lit Slow blink Fast blink LED0 INPUT Input pow

Seite 6 - PROHIBITED

− 11 − EXT.BATTMAIN SW 5.3 External Interfaces UPS back panel No. Name Function ① PC I/F (PC interface) (RS-232C) Allows you to contro

Seite 7

− 12 − 6. Installation CAUTION ! ・ When installing the UPS, carefully follow the instructions in this Instruction Manual. ・ Install the UPS on a

Seite 8

− 13 − 6.4 Preparation Before Installation CAUTION ! ・ Wear insulated gloves and take other precautions when connecting the batteries. Otherwise

Seite 9 - 2.3 Usage Precautions

− 14 − 6.5 Attaching the Stand CAUTION ! ・ Unless the UPS is secured solidly in place, it can shift or fall during seismic events (earthquakes) o

Seite 10 - 2.4 Dealing with Errors

− 15 − 6.6 Mounting a Rack Mount Type UPS CAUTION ! ・ Be careful to avoid straining your lower back when moving and installing the UPS. ・ The UP

Seite 11 - 4. Overview

− 16 − BATTEXT.MAIN SWINPUT plug (seen from prong side) Note When the AC input power is single-wiregrounded, always connect the groundphase to the S

Seite 13

− 17 − BATTEXT.MAIN SW ③ Connect the input power plugs of the load devices to the output terminals. Output terminal capacity Note 125V 1

Seite 14 - 5.3 External Interfaces

− 18 − 8. Preparations Before Operation Check the following items before starting operation: ① Visually inspect the UPS to verify that there is n

Seite 15 - 6. Installation

− 19 − EXT.BATTMAIN SW 9. Operating Procedures 9.1 UPS Startup (Normal Operation) Check that the INPUT indicator has chang

Seite 16 - *Note for removing the screw

− 20 − 9.2 UPS Startup (Battery Power) During a power outage, low voltage, or other trouble with the AC input power to the UPS, you can supply powe

Seite 17 - 6.5 Attaching the Stand

− 21 − 9.3 Outage Simulation Test You should perform a test of whether the UPS operates properly during a power outage. Proper operation is as de

Seite 18 - 6.7 Inserting the Bushings

− 22 − 9.4 UPS Shutdown (Daily) Note Do not touch MAIN SW when you perform a daily shutdown. Leave it set to the “ON” position. *

Seite 19 - 7.1 UPS Wiring

− 23 − 10. User Settings 10.1 Setup Menu Item List You can configure the UPS by setting the menu items in the following list. Configure it accordin

Seite 20

− 24 − Two beeps sound from the buzzer. The setting is saved and the UPS returns to normal operation. 10.2 Setup Menu Operations Set all menu items

Seite 21

− 25 − 11. Maintenance and Inspection 11.1 Daily Inspection Check the control panel LED indicators to confirm that no error is indicated. No other

Seite 22 - 9. Operating Procedures

− 26 − 11.4 Battery Maintenance CAUTION ! ・ Internal maintenance and inspection should be performed only by technically qualified personnel. Elec

Seite 23 - Switch is “OFF”

Introduction Thank you for choosing the SANUPS (E11A102A). SAVE THESE INSTRUCTIONS This manual contains important instructions for E11A102U001 that s

Seite 24 - 9.3 Outage Simulation Test

− 27 − 11.5 Battery Test You can perform automatic and manual tests of the built-in and externally connected batteries. You can do this without sto

Seite 25 - 9.4 UPS Shutdown (Daily)

− 28 − 11.6 Battery Exchange You can exchange the batteries without stopping the load devices. However, this should be done as quickly as possible,

Seite 26 - Do not use this setting

− 29 − ⑦ Attach the battery cover. ⑧ Attach the front panel. ⑨ Rest the remaining battery service life with item ⑯ “Reset r

Seite 27 - 10.2 Setup Menu Operations

− 30 − 11.7 Bypass Fuse Exchange CAUTION ! Always power the UPS off before exchanging the fuse. Failure to do so can cause electric shock. Be car

Seite 28 - 11.3 Parts Replacement

− 31 − 12. Troubleshooting If a problem occurs, check the condition of the equipment and perform countermeasures as listed in the table below. CA

Seite 29 - 11.4 Battery Maintenance

− 32 − Condition Countermeasure No recovery from utility power source failure. Utility power source failure occurs frequently. ・ Check whether MA

Seite 30 - 11.5 Battery Test

− 33 − 13. Alarm Sounds The alarm buzzer emits sound patterns to alert you to failures and error conditions in the UPS. Check the sound pattern and

Seite 31 - 11.6 Battery Exchange

− 34 − 14. Maintenance Bypass Power Supply (Option) You can combine this UPS with an optional Maintenance Bypass Unit. In the event of a failure in

Seite 32

− 35 − 15. Functional Description 15.1 Basic Operation (1) Normal Operation In normal operation, the UPS switches automatically* between the thre

Seite 33 - 11.7 Bypass Fuse Exchange

− 36 − (c) Economy mode The UPS switches to Economy mode when the input power voltage is within a certain range and the output power factor is above

Seite 34 - 12. Troubleshooting

− 1 − 1. Safety Precautions PRECAUTIONS (IMPORTANT SAFETY INSTRUCTIONS) Before installing, operating, performing maintenance or inspecting the UPS,

Seite 35

− 37 − 15.2 Protective Functions (1) Overload Protection If the UPS output is overloaded by exceeding the current capacity of the inverter, such as

Seite 36 - 13. Alarm Sounds

− 38 − 15.3 Protective Function Table The following table shows functions and operations which activate to protect the UPS. The ○ mark indicates li

Seite 37

− 39 − 15.4 Specifications Item Standard or Performance Notes Output capacity 1kVA/0.7kW Cooling system Forced air cooling Phases Single

Seite 38 - 15. Functional Description

− 40 − 16. Warranty Warranty for Use Overseas (North America) 3 Years 1. This product is warranted against electrical failure due defects in m

Seite 39 - Indications by LEDs

− 41 − Appendix Usage notes for SANUPS SOFTWARE STANDALONE When using supplied “SANUPS SOFTWARE STANDALONE”, please note the following instructions

Seite 40 - 15.2 Protective Functions

− 42 − LED blinking for setting up menu For the following two Menu Item, • “Restart time (battery charge rate)” in the E11A Instruction Manual §1

Seite 42 - 15.4 Specifications

− 2 − 1. Installation Precautions CAUTION • The UPS should be installed only by technically qualified personnel. Improper installation can result in

Seite 43 - 16. Warranty

− 3 − 3. Operating Precautions DANGER • Immediately shut the UPS off if it malfunctions, or if an unusual odor or noise is observed. Failure to do so

Seite 44

− 4 − 4. Radio Frequency Interference CAUTION • This equipment has been tested and found to comply with the limits for a Class A digital device, purs

Seite 45 - LED blinks

− 5 − 7. Battery Handling Precautions CAUTION • Risk of explosion if battery is replaced by an incorrect type • Dispose of used batteries accordin

Seite 46

− 6 − 2. For Proper Operation 2.1 Input Power Requirements (1) Make certain that the AC input voltage and frequency correspond to the specified eq

Kommentare zu diesen Handbüchern

Keine Kommentare